본문
| Model | GBW |
|---|---|
| Used | Wiring in high temperature part of Iron works furnace, generator, electric motor, electric furnace |
| Structure | ① Conductor ② Glass fiber double braid ③ Glass fiber braid ④ High heat resistant coating |
Excellent in heat & cold resistance, available in ultra high temp. 200~450℃
(Ni plated Copper wire : 200~250℃, Solid Ni wire : 300~450℃)
Description
- Heat resistance wires composed of glass fibre cross-connections and braided components
- Wildly used as industrial internal wiring and internal wiring in hot environments
Rating
- Temperature range : 200℃/ 300℃/ 400℃
- Voltage : 300V
Property
- Easy to connect devices in narrow and high temperatures with great flexibility
- Excellent rupture stress resistance and environmental stress crack
Jacket Color
200℃ - WH/BK, 300℃ - WH/RD, 400℃ - WH
Technical Data
| Product Range | Conductor | Insulation Thickness |
Nominal Finished Diam. |
Conductor Resistance |
Test Voltage | |
|---|---|---|---|---|---|---|
| Stranding | Out-Diam. | |||||
| SQ(㎟) | No./mm | mm | mm | mm | Ω/km·20℃ | (V/min.) |
| 0.5 | 20/0.18 | 0.9 | 0.5 | 1.9 | 38.60 | AC2000 |
| 0.75 | 30/0.18 | 1.2 | 0.5 | 2.2 | 25.80 | AC2000 |
| 1.25 | 50/0.18 | 1.5 | 0.5 | 2.5 | 15.50 | AC2000 |
| 2 | 37/0.26 | 1.8 | 0.6 | 3.0 | 9.52 | AC2000 |
| 3.5 | 45/0.32 | 2.5 | 0.65 | 3.8 | 5.14 | AC2000 |
| 5.5 | 35/0.45 | 3.1 | 0.65 | 4.4 | 3.50 | AC2000 |
| 8 | 50/0.45 | 3.7 | 0.65 | 5.0 | 2.45 | AC2000 |
| 14 | 88/0.45 | 4.9 | 0.8 | 6.5 | 1.39 | AC2000 |